Description
Vertiv GXT RT+ 1ph UPS, 1.5kVA, input plug IEC60320 C14, 2U, output – 230V, output socket groups (6)C13
Detailed Tech Specification
GXTRT-1500IRT2UXL
Rating
Power Rating
1500 VA / 1350 W
Dimensions (D×W×H)
Unit
470 x 430 x 85
Weight (kg)
Unit
21
Input AC
Input Voltage
230 VAC
Frequency
40Hz ~ 70Hz; Auto Sensing
Input Power Cord
C14
Output AC
Output Voltage
200/208/220/230/240 VAC
Output Receptacles
C13×8
Waveform
Sine wave
Utility(AC) Model Overload
>200% for 250ms; 150- 200% for 2 seconds; 125- 150% for 50 seconds; 105-125% 60 seconds;
Internal Charger
Charging current
Nominal 2.2 A; Maximum 8 A
Battery
Type
Valve-regulated, non-spillable, lead acid
Qty×V×Rating
4 × 12V × 9.0Ah
Recharge Time
4 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries
Only)
Environmental Requirements
Operating Temperature,°F (°C)
+32 to +122 (0 to 50); Operating temperature may be increased to 122°F (50°C with a 10% de-rating of
the output power
Storage Temperature, °F(°C)
–4to +140 (-20 to 60)( contain batteries will be from –15 to 40°C.)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating
Audible Noise
<46dBA max @ 3ft. (1m) front and sides <45dBA max @ 3ft. (1m) rear
Agency
Safety
EN 62040-1:2008+A1:2013;
GS mark;
UL 1778 5th Edition and CSA 22.2 No. 107.1
EMC
EN 62040-2:2006
EN 61000-3-2:2014
EN 61000-3-3:2013
Transportation
ISTA Procedure 1A
Surge Immunity
ANSI C62.41 Category B IEC 61000-4-5 Surges/Lightning
RFI/EMI
CISPR22 Class A