Description
Technical Specifications Nominal Rating (kVA/kW) 10-15-20 30-40 60 80 100-120 160-200
Input Nominal Input Voltage (V) 380/400/415 VAC 3-Phase, 4 Wire Input Voltage Range (V) 110 to 300 VAC @ 50% load; 184 to 276 VAC @ 100% load For 60-100-120-160-200kVA: 305 ~ 478; 208 ~ 304 (output derated below 70%) Nominal Input Frequency (Hz) 50/60 Input Frequency Range (Hz) 40-70 For 60-100-120-160-200kVA: 46Hz ~ 54 Hz @ 50Hz system 56Hz ~ 64 Hz @ 60Hz system Input Power Factor (kW/kVA)* 0.99 Current THD at full linear load (THDi%)* <4
Battery With Internal Batteries Battery Type 12 V, 9 AH 12 V, 9 AH Not Available No of Battery Blocks 32 Without Internal Batteries Battery Type VRLA Charging Current (Max.) 1 to 12 A (Adjustable) 1 to 18 A (Adjustable) 2 to 32 A (Adjustable) 36 A (Adjustable) 54 A (Adjustable) No of Battery Blocks 32-40
Output Nominal Output Voltage (V) 380/400/415 VAC (3-Phase) Nominal Output Frequency (Hz) 50/60 Maximum Active Power (kW) 10-15-20 30-40 60 80 100-120 160-200 Voltage Harmonic Distortion (%) <2% for Linear loads <5% for Non-linear loads <2% for linear loads <4% for non-linear loads <1% for linear loads <5% for non-linear loads <2% for linear loads <4% for non-linear loads Overload Capacity at 25 °C 100% ~ 110%, 60 min; 111% ~ 125%, 10 min; 126% ~ 150%, 1 min; >150%, 200 ms
Efficiency Double Conversion Mode* Up to 95.5% ECO Mode Up to 98.5%
Dimensions and Weight With Internal Batteries Dimensions (D x W x H) in mm 626 x 250 x 826 780 x 300 x 1000 Not Available Weight (kg) 139 250 Without Internal Batteries Dimensions (D x W x H) in mm 626 x 250 x 826 780 x 300 x 1000 1000 x 320 x 800 790 x 360 x 1010 1000 x 430 x 1200 1000 x 600 x 1200 Weight (kg) 43 67 89 113 200 265
General Nosie at 1 m (dBA)* <62 <70 <75 <75 <75 Operating Temperature (°C) 0 ~ 40 Relative Humidity (%RH) 0 to 95, non-condensing Altitude (m) 0 to 1000 without derating Protection level IEC (60529) IP20 General and safety requirements for UPS IEC/EN 62040-1 EMC requirements for UPS IEC/EN 62040-2, Category C3